Energy evaluation and energy savings analysis with the 2 selection of AC systems in an educational building
This paper presents an energy performance assessment on an educational building in Barranquilla, Colombia. The electricity consumption performance was assessed using the software DesignBuilder for two different Air Conditioning (AC) systems. The current electricity intensity is 215.3 kWh/m2 -year an...
- Autores:
-
BALBIS MOREJON, MILEN
Cabello Eras, Juan José
Rey-Martínez, Francisco Javier
Rey Hernandez, Javier M
- Tipo de recurso:
- Article of journal
- Fecha de publicación:
- 2021
- Institución:
- Corporación Universidad de la Costa
- Repositorio:
- REDICUC - Repositorio CUC
- Idioma:
- eng
- OAI Identifier:
- oai:repositorio.cuc.edu.co:11323/8579
- Acceso en línea:
- https://hdl.handle.net/11323/8579
https://doi.org/10.3390/su13147527
https://repositorio.cuc.edu.co/
- Palabra clave:
- Energy efficiency indicators
HVAC systems
Energy savings
Life-cycle cost
Building energy
Indicadores de eficiencia energética
Sistemas de climatización
Ahorros de energía
El costo del ciclo de vida
Energía del edificio
- Rights
- openAccess
- License
- CC0 1.0 Universal
Summary: | This paper presents an energy performance assessment on an educational building in Barranquilla, Colombia. The electricity consumption performance was assessed using the software DesignBuilder for two different Air Conditioning (AC) systems. The current electricity intensity is 215.3 kWh/m2 -year and centralized AC systems with individual fan coils and a water chiller share 66% of the total consumption and lighting at 16%. The simulation of the AC technology change to Variable Refrigerant Flow (VRF) resulted in an improvement of 38% in AC energy intensity with 88 kWh/m2 -year and significant savings in electricity consumption and life-cycle cost of AC systems in buildings. |
---|