Statistical analysis of design variables in a chiller plant and their influence on energy consumption and life cycle cost
An appropriate design of a chiller plant is crucial to guarantee highly performing solutions. However, several design variables, such as type of systems, total cooling capacity, and hydraulic arrangement, need to be considered. On the one hand, at present, different technical criteria for selecting...
- Autores:
-
diaz torres, yamile
Gullo, Paride
Hernández Herrera, Hernán
Torres del Toro, Migdalia
Álvarez Guerra, Mario A.
Silva Ortega, Jorge I
Speerforck, Arne
- Tipo de recurso:
- Article of investigation
- Fecha de publicación:
- 2022
- Institución:
- Corporación Universidad de la Costa
- Repositorio:
- REDICUC - Repositorio CUC
- Idioma:
- eng
- OAI Identifier:
- oai:repositorio.cuc.edu.co:11323/9841
- Acceso en línea:
- https://hdl.handle.net/11323/9841
https://repositorio.cuc.edu.co/
- Palabra clave:
- Chiller
Design variables
Energy saving
Life cycle cost
Pearson’s correlation
Spearman’s correlation
- Rights
- openAccess
- License
- Atribución 4.0 Internacional (CC BY 4.0)
Summary: | An appropriate design of a chiller plant is crucial to guarantee highly performing solutions. However, several design variables, such as type of systems, total cooling capacity, and hydraulic arrangement, need to be considered. On the one hand, at present, different technical criteria for selecting the most suitable design variables are available. Studies that corroborate the influence of the design variables over the operational variables are missing. In order to fill this knowledge gap, this work proposes a statistical analysis of design variables in chiller plants operating in medium- and large-scale applications and evaluates their influence on energy consumption and life cycle cost (LCC) under the same thermal demand conditions. A case study involving 138 chiller plant combinations featuring different arrangements and a Cuban hotel was selected. The results suggested that the total chiller design and cooling capacity distribution among chillers have a significant influence on the energy consumption of the chiller plant with a Spearman’s Rho and Kendall Tau (τ) correlation index value of −0.625 and 0.559, respectively. However, with LCC, only the cooling capacity distribution among the chillers had a certain influence with a Kendall Tau correlation index value of 0.289. As for the considered total cooling capacity, the applied statistical test showed that this design variable does not have any influence on performing the chiller plant. |
---|